CWI D1.1 Inspection practice questions
Applying AWS D1.1 Clause 8: inspector duties, visual acceptance criteria, NDT requirements and acceptance of discontinuities. This domain is about 30% of the exam. Try each question, then open the answer.
Read the D1.1 Inspection study guide
Question 1
- Five years as a production welder, with no Engineer acceptance
- Current AWS CWI certification under AWS QC1
- ASNT Level II certification in radiography
- A current ASME Section IX welder qualification
Show answer
Answer: B. Current AWS CWI certification under AWS QC1
D1.1 accepts an inspector who holds AWS CWI certification under QC1, or CWB certification under CSA W178.2. It also accepts an engineer or technician whom the Engineer accepts as competent through training or experience. See the Clause 8, Part A inspector qualification provisions.
Question 2
- Require a demonstration test or full requalification
- Revoke the welder's AWS certification on the spot
- Nothing, because welder qualification lasts indefinitely
- Require the contractor to switch every joint to a prequalified WPS
Show answer
Answer: A. Require a demonstration test or full requalification
Sometimes there is reason to doubt a qualified welder's work. Clause 8 then lets the inspector ask for a demonstration of ability, such as a fillet weld break test. The inspector may instead require complete requalification under Clause 6. See the Clause 8 provisions on inspection of welder qualifications.
Question 3
- 1/32 in. (1 mm)
- 1/16 in. (2 mm)
- No limit if the weld is ground
- 0.01 in. (0.25 mm)
Show answer
Answer: D. 0.01 in. (0.25 mm)
For cyclically loaded connections, undercut in primary members has two limits. It must be no deeper than 0.01 inch when the weld is transverse to tensile stress under any design loading. In all other cases the limit is 1/32 inch.
Question 4
- Acceptable: one pore is under the 3/8 in. per inch limit
- Acceptable if the pore is under 3/32 in. in diameter
- Rejectable: this weld may have no visible piping porosity
- Acceptable: groove weld porosity is judged by RT
Show answer
Answer: C. Rejectable: this weld may have no visible piping porosity
Table 8.1 allows no visible piping porosity in CJP groove welds in butt joints transverse to the computed tensile stress. See Table 8.1, porosity.
Question 5
- It is rejected regardless of length
- It is accepted regardless of length
- It is accepted if shorter than 3/4 in.
- It is referred to RT for confirmation
Show answer
Answer: A. It is rejected regardless of length
D1.1 UT acceptance tables sort indications into severity classes based on indication rating, thickness and probe angle. Class A is rejected whatever its length; Class D is accepted whatever its length or location; Classes B and C have length limits.
Question 6
- Acceptable: 1/32 in. is within the limit for this thickness
- Rejectable: any undercut is limited to 2 in. in each 12 in. of weld
- Rejectable: no undercut is allowed under 1 in. thick
- Acceptable only after the undercut is ground smooth
Show answer
Answer: A. Acceptable: 1/32 in. is within the limit for this thickness
For material under 1 inch thick, Table 8.1 allows undercut up to 1/32 inch for any length. The allowance of 2 inches in any 12 inches applies only to deeper undercut, up to 1/16 inch. See Table 8.1, undercut, statically loaded column.
Question 7
- Acceptable: the underrun and its length are within limits
- Rejectable: a 3/16 in. fillet may not run under at all
- Rejectable: the allowed underrun is 1/32 in. for this size
- Acceptable only if the inspector measures the throat
Show answer
Answer: A. Acceptable: the underrun and its length are within limits
For a 3/16 in. fillet, the allowed underrun is 1/16 in., and 1/8 in. measured is exactly 1/16 in. under. The undersized length is 2 in., which is under 10% of 30 in. (3 in.). See Table 8.1, undersized welds.
Question 8
- Accepted, because UT results take priority
- Accepted if the crack is shorter than 1/8 in.
- Accepted once a second UT technician confirms the first result
- Rejected, because it must also meet the visual criteria
Show answer
Answer: D. Rejected, because it must also meet the visual criteria
Welds that get NDT must also meet the visual acceptance criteria. Table 8.1 rejects any crack, whatever its size. See Clause 8, Part C, and Table 8.1, cracks.
Question 9
- 1/8 in. to 2 in.
- 1/4 in. to 4 in.
- 5/16 in. to 8 in.
- 1/2 in. to 12 in.
Show answer
Answer: C. 5/16 in. to 8 in.
D1.1's UT procedures for groove welds and their HAZs cover thicknesses from 5/16 inch to 8 inches. Thinner or thicker material is outside the standard procedure. See Clause 8, Part F.
Question 10
- -7 dB
- -5 dB
- -2 dB
- +1 dB
Show answer
Answer: B. -5 dB
The rating is d = a - b - c. The attenuation factor c is 2 dB per inch of sound path beyond the first inch: 2 x (2.5 - 1) = 3 dB. So d = 48 - 50 - 3 = -5 dB. See the Clause 8, Part F provisions on indication rating.
Question 11
- On the film side of the joint
- Inside the film cassette
- On the source side of the joint
- On the weld centerline, film side
Show answer
Answer: C. On the source side of the joint
IQIs are normally placed on the source side, where they show sensitivity under the least favorable conditions. Film-side placement is an exception for cases where the source side cannot be reached. See Clause 8, Part E.